uCAD

Stairs by floor height · 2.55 m

Stairs for a 2.55 m floor-to-floor height

2.55 m (255 cm) from floor to floor takes 15 risers of 17 cm and 14 treads 29 cm deep: a pitch of 30°, and two risers and a going make 63 cm, an easy stride. A straight flight is 4.06 m long and needs an opening of 3.75 m in the floor above.

15risers
17 cmeach riser
29 cmgoing (tread depth)
14treads (the last riser is up to the floor)
30°pitch
4.06 mrun of a straight flight
opening 3.75 m riser 17 cm going 29 cm 30° run 4.06 m 2 m clear over every nosing

How it’s worked out

The fewest risers that keep each at most 18 cm (7″) high, all the same: 2.55 m ÷ 15 = 17 cm. The going follows the stair builders’ rule that two risers and a going make a stride of about 63 cm (25″). There is one tread fewer than risers: the last riser goes up to the upper floor itself.

If 2.55 m is your ceiling height, the stair is taller: add the floor above it, usually 25–35 cm — see stairs for 2.85 m.

More or fewer steps

Fewer risers make a shorter, steeper stair; more make a longer, easier one.

RisersEach riserGoingPitchRun of a straight flightHow it walks
1319.6 cm25 cm38°3.00 msteeper, fewer steps
1418.2 cm27 cm34°3.51 mcomfortable
1517 cm29 cm30°4.06 mcomfortable (drawn here)
1615.9 cm31 cm27°4.65 mcomfortable

Limits differ by country: England’s Approved Document K allows a rise up to 220 mm and a pitch up to 42° in a home, Germany’s DIN 18065 up to 200 mm, and both ask for 2.0 m of headroom. Check the code that applies to yours.

This stair in each layout

Each drawn for 2.55 m: the flights 1.00 m wide, the spiral 1.60 m across, the square one in a 1.80 m stairwell. The size is over the treads. Pick one for its plan, its sizes and its parts.

Change anything

A different width, a turn the other way, closed risers, a steel frame: open the stair in uCAD and set it in the panel, or tell the AI what the stair has to fit into.

Open it in uCADStair calculator

Other heights

Other heights: 2.50 m · 2.60 m · all heights

Measured between finished floors. A few centimetres change the riser, not the count, until a riser passes 18 cm.